- Journal of Thermal Engineering
- Vol: 1 Issue: 7 Special Issue
- EXPERIMENTAL PERFORMANCE OF R134a AND R152a USING MICROCHANNEL CONDENSER
EXPERIMENTAL PERFORMANCE OF R134a AND R152a USING MICROCHANNEL CONDENSER
Authors : V. W. Bhatkar
Pages : 0-0
Doi:10.18186/jte.91982
View : 15 | Download : 0
Publication Date : 2016-06-06
Article Type : Other
Abstract :An experimental performance study on vapour compression refrigeration system with R134a and drop in substitute R152a with aluminium microchannel condenser was carried out for condensation temperature of 48°C while evaporation temperature varied from -10 to 15°C. Refrigerant charge of R152a was reduced by 40% over R134a with the microchannel condenser. Performance parameters like work input to the compressor, coefficient of performance, refrigerating capacity, condenser capacity and the product of the overall heat transfer coefficient & surface area of the condenser are plotted and results are discussed.Keywords :