- Turkish Journal of Electrical Engineering and Computer Science
- Vol: 28 Issue: 2
- Investigation on leakage current, erosion, and hydrophobic performance of high-voltage insulator coa...
Investigation on leakage current, erosion, and hydrophobic performance of high-voltage insulator coatings of different thicknesses
Authors : Suat Ilhan, Zeynelabidin Aslan
Pages : 1197-1207
Doi:10.3906/elk-1907-234
View : 6 | Download : 2
Publication Date : 9999-12-31
Article Type : Makaleler
Abstract :Room-temperature vulcanizing RTV silicone rubber is used as a high-voltage insulator coating to enhance the pollution performance of conventional insulators, and the electrical performance of RTV coating depends on the several parameters. The present study shows the effects of the thickness on the leakage current, erosion, and hydrophobic performance of high-voltage insulator coating. Several different thicknesses of RTV silicone rubber were taken into consideration on porcelain substrates. Erosion and leakage current performances of the samples were evaluated by using inclined-plane tests IPTs based on the IEC 60587 standard. Eroded masses and fundamental and harmonic components of the leakage currents were investigated with respect to coating thicknesses. On the other hand, hydrophobic features of the samples were evaluated by using dynamic drop tests DDTs with regard to CIGRE TB442 documentation. Time to loss of hydrophobicity and the level of the leakage currents were investigated in DDTs considering the thicknesses.Keywords : RTV coating, hydrophobicity, eroded masses, inclined-plane tests, dynamic drop test