- Thermodynamic Analysis of an Intercity Bus Air-Conditioning System Working with HCFC, HFC, CFC and H...
Thermodynamic Analysis of an Intercity Bus Air-Conditioning System Working with HCFC, HFC, CFC and HC Refrigerants
Authors : Mehmet BİLGİLİ, Ediz CARDAK, Arif Emre AKTAS, Firat EKİNCİ
Pages : 29-43
Doi:10.18245/ijaet.490002
View : 8 | Download : 4
Publication Date : 2019-05-20
Article Type : Research
Abstract :The purpose of this study is to perform thermodynamic analysis of an intercity bus air-conditioning (ICBAC) system working with hydrochlorofluorocarbon (HCFC), hydrofluorocarbon (HFC), chlorofluorocarbon (CFC) and hydrocarbon (HC) refrigerants. For this aim, an intercity bus with a busload of 56 passengers, which is thought to motion in the Adana province of Turkey, was selected. R404A, R410A, R502, R507, R22, R290, R134a, R500 and R600a were selected as different HCFC/HFC/CFC/HC refrigerant types in the ICBAC system. Useful and reversible works of compressor, coefficient of performance (COP), exergy efficiency and exergy destructions of the entire ICBAC system and its each sub-unit were obtained. The results showed that the performance of the ICBAC system was significantly influenced by changing the refrigerants. However, R600a refrigerant based on hydrocarbon was found as a refrigerant to have minimum total exergy destruction, maximum exergy efficiency and maximum COP compared to other refrigerants used in the ICBAC system with the same amount of cooling load and the same climatic condition.Keywords : Air-conditioning, Refrigerants, Air mixing ratios (MR), Exergy, Exergy efficiency